DUNGS Pressure Switch ÜB/NB…A2 Series

The pressure limiters ÜB…A2 and NB… A2 are compact pressure switches as per EN 1854 for DUNGS multiple actuators. The pressure switches are suitable for switching a circuit on, off or over on changes in actual pressure value relative to the set reference value. The reference valve (switching point) can be set easily and quickly by means of a setting wheel provided with a scale without the use of a pressure gauge.Pressure switches for DUNGS multiple actuators GasMultiBloc and DMV double solenoid valve. Various mounting options directly on housing or by means of an adapter. Standard mounting on valve housing on the inlet side via threaded flange. Suitable for gases of families 1,2,3 and other neutral gaseous media.

Max. Operating pressure: 500/600 mbar

Model Versions of DUNGS ÜB…A2, NB…A2 pressure limiters are the control unit responds to pressure. Interlock is performed when the set reference value is exceeded or undershot. The “Locked” switching state is indicated by a glow lamp. Restart is only possible by activating the reset button on the setting wheel of the pressure limiter after the operating pressure is attained :

  • ÜB…A2: Switches on and locks if the set pressure value is exceeded.
  • NB…A2: Switches on and locks if the pressure is lower than the set pressure value.
ÜB…A2 Model :Settings Range [mbar]Degree Protection
ÜB 50 A25 mbar – 50 mbarIP 54
ÜB 150 A230 mbar – 150 mbarIP 54
ÜB 500 A250 mbar – 500 mbarIP 54
NB..A2 Model :Settings Range [mbar]Degree Protection
NB  50 A25 mbar – 50 mbarIP 54
NB 150 A230 mbar – 150 mbarIP 54
NB 500 A250 mbar – 500 mbarIP 54