Honeywell R7800 Flame Amplifier
Honeywell R7800 Series Flame Amplifiers come in several models with various configurations.
Flame failure response time of 0.8 or 1 second; or 2.0 or 3.0 seconds, depending on the amplifier and relay module selected. Plug-in to 7800 series Relay Module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks measure amplifier flame signal voltage.
- 0 to 5.0 Vdc Flame signal strength reading range.
- Plug-in Flame Signal Amplifiers Types with Color coded label identifies :
- Green – rectification
- Red – infrared
- Purple – ultraviolet
- Blue – pulsed rectification
- White – optical
Honeywell R7800 Series Flame Amplifiers Model Versions :
- R7847A1033 Flame Amplifier
- R7847A1082 Flame Amplifier
- R7849A1023 Ultraviolet Flame Amplifier
- R7861A1026 Self-Check Ultraviolet Flame Amplifier
* For any order enquiries, please consult JATI